The initial type test of a product is a set of technical and functional checks carried out on a representative sample of a product to verify that it complies with specific regulatory, technical or safety requirements, prior to the start of series production or placing on the market.
In practice, its purpose is to:
- Verify that the product design complies with applicable technical standards
- Ensure that the product meets the required safety, quality and performance criteria.
- Provide the basis for the product’s certification, where applicable.
Discover the tests carried out by M.M.

REACTION TO FIRE
Reaction to fire refers to the degree to which a combustible material participates in the fire to which it is exposed. It is a property of the material.
Standard EN 13501-1 defines the classification criteria based on the results of reaction-to-fire tests.
The classification report P 0958/16-530-3 issued by ZAG, based on the test results, assigns the open grating with IFR formulation the fire reaction class Bfl (where the subscript fl stands for flooring) and the smoke emission class s1.
The classification report 386900 issued by Istituto Giordano, based on the test results, assigns the grating with double surface laminate and IFR formulation the fire reaction class Bfl (where the subscript fl stands for flooring) and the smoke emission class s1.
EN 13501 fire classification tests are also carried out on different formulations and geometries.
For certain countries and fields of application, fire reaction classification may be required based on other standards (e.g. ASTM).
Test reports available
| STANDARD | TEST | number | isued by | type | date |
| EN 13501-1 | Reaction to fire IFR formulation SCH52/100 | P 0958/16-530-3 | ZAG | CLASSIFICATION REPORT | 05/04/17 |
| EN 13501-1 | Reaction to fire IFR formulation SCH38/38DC | 386900 | ISTITUTO GIORDANO | CLASSIFICATION REPORT | 22/09/21 |
| EN 13501-1 | Reaction to fire VFR formulation SCH12/38 | 387494 | ISTITUTO GIORDANO | CLASSIFICATION REPORT | 07/10/21 |
| EN 13501-1 | Reaction to fire IFR formulation SCH12/30 | 359608 | ISTITUTO GIORDANO | CLASSIFICATION REPORT | 20/03/19 |
| EN 13501-1 | Reaction to fire IFR formulation SCH38/25C | 359594 | ISTITUTO GIORDANO | CLASSIFICATION REPORT | 20/03/19 |
| ASTM E84-98 | Reaction to fire | 105255978SAT-001 | INTERTEK | TEST REPORT | 07/02/23 |
| N FP 92-507 | Fire behavior | P134122 – DE/1 | LNE | TEST REPORT | 02/12/14 |
| NF F 16-101 / 16-102, NF X 70-100 / 10-702, STM-S-001 | Smoke emission | P134122 – DE/2 | LNE | TEST REPORT | 02/12/14 |

ELECTRICAL CHARACTERISTICS
MM.M. has tested the following electrical characteristics of STANDARD line gratings with IFR formulation:
- Surface and transverse electrical resistivity and resistance Rs and Rt
- Electrical resistivity and safety resistance to ground, human body model
- Dielectric strength at rated voltage
Based on the results obtained (resistivity greater than 200 MΩ, current absorption of approximately 300 μA), the material can be defined as an excellent insulator compliant with safety standards.
Test reports available – INSULATING
| STANDARD | TEST | number | issued by | type | date |
| EN 61340-2.3 ISO 1853 IEC 60167 HD 568 S1 | Surface and transverse electrical resistivity and resistance Rs and Rt | 604/12.2011 | ELECTRA | TEST REPORT | Dic. 2011 |
| IEC 61340-4-5 CEI 64-4/8/6 IEC 60167 HD 568 S1 | Electrical resistivity and safety resistance to ground, human body model | ||||
| ASTM D 149-97a | Dielectric strength at rated voltage | ||||
| CEI EN 61340-4-1:2005 | Assessment of vertical, point-to-point and to-ground electrical resistance | 358728 | ISTITUTO GIORDANO | TEST REPORT | GEN 2019 |
M.M. has carried out the following tests on gratings of the CONDUCTIVE line:
Surface and volume electrical resistivity
Surface and transverse electrical resistivity with a 10 Volt DC test voltage. Based on the tests performed, the samples show very low surface and transverse electrical resistivity and are therefore classified as excellent conductors.
Safety electrical resistance to ground, human body model
Electrical safety with direct ground connection at 500 Volt DC.
It is recommended to use a ground connection with a resistance greater than 1 MΩ.
Electrical safety with ground connection through a resistance of 2 MΩ.
Based on the tests performed, the samples comply with the standards (it is recommended to use resistances in the range of 1 MΩ to 5 MΩ).
A walking test with treading was simulated, using dissipative antistatic safety footwear, on the grating samples under test, both with and without a ground connection. In both cases no electrostatic charge generation occurred. Both samples are therefore fully classified as non-generators of electrostatic charge from foot traffic.
Test reports available – CONDUCTIVE
| STANDARD | TEST | number | issued by | type | date |
| EN 61340-2.3 IEC 61340-4.1 ISO 1957 IEC 61340-4.5 | Surface and volume electrical resistivity | 481/12.2008 | ELECTRA | TEST REPORT | Dic. 2008 |
| CEI 64-4/8/6 IEC 61340-5-1 IEC 61010-1 | Safety electrical resistance to ground, human body model |

ANTI-SLIP
DIN 51130 is a German standard concerning the slip resistance of flooring surfaces under working conditions involving the presence of lubricants, such as oils or greases. It is particularly relevant for industrial environments.
What does DIN 51130 measure?
It measures the critical angle of inclination beyond which a person (wearing standard footwear) begins to slip while walking on an inclined plane covered with the material being tested.
Slip resistance classes (R)
The standard classifies materials into classes from R9 to R13, where:
- R9 = minimum slip resistance
- R13 = maximum slip resistance
The meaning of the two parameters R and V is indicated in the tables below.
| R Indicates the angle of inclination reached in the test. | over 6° up to 10°: R 9 over 10° up to 19°: R 10 over 19° up to 27°: R 11 over 27° up to 35°: R 12 over 35°: R 13 |
| V Represents the drainage space determined by the surface relief. |
The values resulting from tests carried out according to DIN 51130 on open and covered gratings with different surface finishes are reported below.
Also indicated is the assessment contained in the “expert opinion” issued by ZAG following the anti-slip tests carried out on the gratings using the pendulum method.
Test reports available
| STANDARD | finish | number | issued by | type | date | LEVEL |
| DIN51130 | SMOOTHLISCIO | 4939/03 | CENTRO CERAMICO | TEST REPORT | 21/11/03 | R10 |
| DIN51130 | MENISCUS | 4937/03 | CENTRO CERAMICO | TEST REPORT | 21/11/03 | R13 |
| DIN51130 | QUARTZ | 5782/03 | CENTRO CERAMICO | TEST REPORT | 21/11/03 | R13 |
| DIN51130 | COVERED QUARTZ | 4936/03 | CENTRO CERAMICO | TEST REPORT | 21/11/03 | R13 V4 |
| DIN51130 | COVEREDCHEQUERED TYPE2 | 7873/17 | CENTRO CERAMICO | TEST REPORT | 27/09/17 | R10 V4 |
| PENDULUM TEST | SMOOTH, MENISCUS, QUARTZ, COVERED QUARTZ | P589/09-480-1 | ZAG | TEST REPORT | 05/08/10 | |
| M589/09/650-2 | ZAG | EXPERT OPINION | 27/02/11 | |||

AGEING RESISTANCE
There is no possibility of correlating the duration of artificial ageing tests with the expected actual service life of a product exposed to real conditions.
Test results provide reasonable indications when comparing different samples or mechanical and/or physical characteristics; in these cases, the results are more directly interpretable.
GRATINGS
TEST ACCORDING TO ASTM G154-06
Exposure for 1500 hours to UV lamp irradiation of 0.71 W/m² at a wavelength of 313 nm, with cyclic temperature and humidity variation.
At the end of the test, the sample undergoes a visual inspection and a grey scale check to assess color deterioration.
PROVA SECONDO UNI ISO 9142/04
TEST ACCORDING TO UNI ISO 9142/04
Cycle D3
The test is carried out keeping the sample inside a forced-ventilation climatic chamber, under the following conditions:
– 15 hours at a temperature of 40±2°C with relative humidity of 90±3%
– the temperature is brought to -20±3°C over 60 minutes, and held for 2 hours
– the temperature is brought to 70±3°C and 50±5% RH over 60 minutes, and held for 4 hours
– the temperature is brought to 40±3°C over 60 minutes
Repeated for 21 cycles (504 hours in total), the sample undergoes a visual inspection and a grey scale check to assess color deterioration.
The UV ageing test was passed with a grade of five on the grey scale and with no defects observed. After the hot/cold cycles, the gratings show no residual defects.
The results of tests carried out by ZAG (Slovenian National Building and Civil Engineering Institute) – report no. P589/09-460-01 INITIAL TYPES TESTING OF GRP FOR MOULDED GRATINGS – on samples taken from old supply batches showed that no sample exhibited significant variation in mechanical characteristics (flexural strength and modulus of elasticity) between old and new samples.
PROFILES
For isophthalic resin profiles, the series of tests carried out on samples for CE marking of stairs is available.
These tests involve flexural strength and impact resistance testing before and after accelerated ageing through exposure to a Xenon lamp.
TEST ACCORDING TO UNI EN ISO 4892:2006 + A1:2009
Exposure of 500 hours
Irradiance at 340 nm: 0.50 W/m²
Average black panel temperature: 65 ± 3°C
Test cycle: 102 minutes of light and 18 minutes of water spray.
Charpy impact resistance test (UNI EN ISO 179:2010) and flexural strength test (UNI EN ISO 14125-98) before and after the artificial ageing cycle.
To be acceptable (according to EN 14396:2004), the variation must be less than 20%.
Test results show a 7.9% increase in impact resistance and a 12.4% decrease in modulus of elasticity.
Test reports available – GRATINGS
| STANDARD | TEST | number | issued by | type | date |
| ASTM G154-06 | Accelerated ageing with UV lamp | 83855/1 IFR 83854/1 ISO | CATAS | TEST REPORT | 26/09/2007 |
| UNI EN ISO 9142/04 | Heat, cold and humidity exposure cycle | 83857/2 IFR 83858/2 ISO 838598/2 ISO | CATAS | TEST REPORT | 06/09/2007 |
| ASTM D 790 | Determination of mechanical properties at low temperature (-30°C) | L15-8390-001 | TEC Eurolab | TEST REPORT | 11/12/2015 |
| INITIAL TYPES TESTING OF GRP FOR MOULDED GRATINGS | P589/09-460-01 | ZAG | 20/09/2010 | ||
Test report disponibili PROFILI
| NORMA | TEST | number | issued by | type | date |
| ASTM G154-06 | Accelerated ageing with UV lamp | 83859/1 PRO | CATAS | TEST REPORT | 26/09/2007 |
| UNI EN ISO 9142/04 | Heat, cold and humidity exposure cycle | 838598/2 ISO | CATAS | TEST REPORT | 06/09/2007 |
| TEST COMPARATIVI | |||||
| UNI EN ISO 4892-06+A1 | Xenon lamp irradiation | 153315/5 | CATAS | TEST REPORT | 23/04/2013 |
| UNI EN ISO 179:2010 | Impact resistance (Charpy) | 153315/1 | CATAS | TEST REPORT | 23/04/2013 |
| 153315/3 | CATAS | TEST REPORT after Xeno | 23/04/2013 | ||
| UNI EN ISO 14125-98 | Determination of mechanical properties | 153315/2 | CATAS | TEST REPORT | 23/04/2013 |
| 153315/4 | CATAS | TEST REPORT after Xeno | 23/04/2013 | ||

FRANGIBILITY
The perimeter fencing solution with FRP posts and mesh was tested at a dedicated laboratory and found compliant with the frangibility requirements set out in ICAO Doc 9157, Aerodrome Design Manual – Part 6 – Frangibility.